Oxford Method Research Programme

Fire Resisting Standards 2M/3M

mandervillelogo

     Comparison Table

 

ELEMENTS OF STRUCTURE                  height of top floor not more than 5 metres above ground level for Single and Two storey 2M and 3M buildings BRE Assessment Building Regulations Approved Document B Appendix A Table A1 and A2
 
Fire resistance in Minutes
External Walls - metal external cladding, metal angle supports & plasterboard internal lining
25
30*
Column Casing - steel columns with asbestos or marinite casing (see BRE report)
90
30*
Fire Resisting Suspended Ceilings - steel 'J' bars, screwed asbestos ceiling tiles
30
30
Internal Partitions - timber studs with 2 layer 12.5 mm plasterboard both sides
30 to 60 depending on fixing details
30
Precast Concrete Floor Slabs - including slabs with suspended ceiling beneath
30
30
Roof Construction
n/a
n/a
Internal solid masonry wall construction - lift wells, plant rooms, boiler rooms
60
30
* increased to 60 minutes for compartment walls separating buildings
 
 